Vallecitos Water District
Home Sitemap ContactApproved Materials
APPROVED MATERIALS LIST
SERVICE MATERIALS
DECEMBER 2021
SIZE |
DESCRIPTION |
MANUFACTURER & MODEL NUMBER |
NOTES |
CORPORATION STOPS |
|||
1" |
MIP x CTS Comp ball corp stop |
Ford: FB 1100-4Q
McDonald: 74704-BQ |
No lead |
2" |
MIP x CTS comp ball corp stop |
Ford: FB 1100-7Q McDonald: 74704-BQ |
No lead |
1" |
MIP x FIP ball corp stop * |
Ford: FB 1700-4 McDonald: 73149-B |
No lead |
2" |
MIP x FIP ball corp stop * |
Ford: FB 1700-7 McDonald: 73149-B |
No lead |
* High pressure assembly only, above 175 psi |
|||
ANGLE METER STOPS |
|||
1" |
CTS ball angle meter stop |
Ford: BA43-444WQ McDonald: 74602-BQ |
No lead |
2" |
CTS ball angle meter stop |
Ford: BFA43-777WQ McDonald: 74602-BQ |
With elongated holes No lead |
1" |
FIP ball angle meter stop* |
Ford: BA13-444W McDonald: 74604-B |
No lead |
2" |
FIP x flg. ball angle meter stop* |
Ford: BFA13-77W McDonald: 76101-MW |
With elongated holes No lead |
* High pressure assembly only, above 175 psi |
|||
ADAPTERS |
|||
1" |
MIP x CTS comp adapter |
Ford: C84-44Q McDonald: 74753-Q |
No lead |
2" |
MIP x CTS comp adapter |
Ford: C84-77Q McDonald: 74753-Q |
No lead |
BALL VALVES |
|||
1" |
FIP ball valve |
Ford: B11-444 McDonald: 76101 W |
No lead |
2" |
FIP ball valve |
Ford: B11-777 McDonald: 76101 W – SHDLB |
No lead |
1" |
FIP ball valve with handle |
Ford: B11-444W with HB34S McDonald: 76101W - SHDLB |
No lead |
2" |
FIP ball valve with handle |
Ford: B11-777W with HB67S McDonald: 76101W - SHDLB |
No lead |
¾” |
FIP x meter nut ball valve with handle |
Ford: B13-332W with HB34S McDonald: 76101MW - HDLB |
No lead |
1" |
FIP x meter nut ball valve with handle |
Ford: B13-444W with HB34S McDonald: 76101MW - HDLB |
No lead |
2" |
FIP x flg ball valve with handle |
Ford: BF13-777W with HB67S McDonald: 76101MW - SHLB |
No lead |
SADDLES |
|||
1” & 2” IPT outlet |
ACP, DIP |
Jones: J-979 McDonald: 3826 |
Bronze body w/bronze double straps |
1” & 2” IPT outlet |
PVC (C-900) |
Jones: J-969W McDonald: 3846 |
Bronze body with Stainless Steel 4 Bolt Single Strap |
PRESSURE REGULATING VALVES |
|||
¾”, 1" & 2" |
Wilkins: #600HR* |
No lead |
|
* All bronze body and bell housing and S.S. replaceable seat |
|||
COPPER TUBING |
|||
1" & 2" |
Type “K” soft |
||
WATER METERS |
|||
¾” (x 7 ½”) |
Box/vault sets shall have TR/PL registers, cu.ft. x 100 |
Sensus iPERL |
7 ½” Lay length (MFR date within two years of scheduled unlock date) |
1" |
Box/vault sets shall have TR/PL registers, cu.ft. x 100 |
Sensus iPERL |
(MFR date within two years of scheduled unlock date) |
1 ½” |
Box/vault sets shall have TR/PL registers, cu.ft. x 100 |
Invensys Omni T² |
Flanged ends, verify type (MFR date within one year of scheduled unlock date. Save Tags) |
2" |
Box/vault sets shall have TR/PL registers, cu.ft. x 100 |
Invensys Omni T² |
Flanged ends, verify type (MFR date within one year of scheduled unlock date. Save Tags) |
3" – 6” meters shall be Invensys Omni T². Larger meters as approved by VWD |
|||
GATE VALVES |
|||
3" - 24" |
All ductile iron body and bonnet, resilient wedge with factory epoxy with low zinc stem |
AVK, Clow, Mueller |
* AWWA C-515 * Mfr date within one year of installation/Holiday-free |
BUTTERFLY VALVES |
|||
CL 250: All flanged, ductile iron body, rubber in the body, with factory epoxy inside |
Pratt |
* AWWA C-504 * Mfr date within one year of installation/Holiday-free |
|
COMBINATION AIR AND VACUUM VALVES |
|||
1" |
** |
APCO: 143-C A.R.I.: D-040 |
APCO: High Pressure ONLY Above 175 PSI |
2" |
** |
APCO: 145-C A.R.I.: D-040 |
APCO: High Pressure ONLY Above 175 PSI |
3" |
** |
APCO: 147-C |
Per approved plans |
4" |
** |
APCO: 149-C |
Per approved plans |
6" |
** |
APCO: 150-C |
Per approved plans |
** For APCO, all internal parts shall be stainless steel |
|||
AUTOMATIC CONTROL VALVES |
|||
Cla-Val |
|||
DETECTOR CHECK VALVES |
|||
2" - 10" |
Cla-Val, Febco, Wilkins, Watts, Ames, Conbraco * (all with iPERL bypass meter) *Individual model submittal will require approval by the District. |
Double check detector or reduced pressure detector, depending on degree of hazard |
|
VAULT LIDS |
|||
Type “J” or “JD” |
Bilco, Syracuse |
With all S.S. hardware, torsion bars, recessed locking hasp, hinged reading lid |
|
FIRE HYDRANTS |
|||
Residential Areas |
One 4" & one 2 ½” outlets |
Jones: J-3700 or J-4040C Clow: 2050 or 850 |
Bronze or Iron, 6 hole, 7/8” drilling, plastic caps |
Multi-Res, Commercial & Industrial Areas |
Two 4" & one 2 ½” outlets |
Jones: J-3775 or J-4065C Clow: 2065 or 865 |
Bronze or Iron, 6 hole, 7/8” drilling, plastic caps |
METER BOXES & LIDS |
|||
3/4" Meter |
Polymer Concrete #4 ½ (20K) |
Armorcast: Box: A6000485 & Lid: A6000484-H2 or J & R: P-W4 ½-20K (DWG:4008) |
|
1"-2" Meter |
Polymer Concrete #6B (20K) |
Armorcast: Box: A6001640PCX12, Cover: A6001947TDZ-H2 & Lid, Insert Lid: A60004842T or J & R: P-W6B-20K (DWG:6073) |
|
#4 ½ meter boxes shall have one-piece polymer lids rated 20K max. load, with 2” touch read hole #6 meter boxes shall have two-piece polymer lids rated 20K max. load, with 2” touch read hole |
|||
TAPPING SLEEVES |
|||
Size on Size |
Cut-in flanged tee with valves and flex couplings |
Fire and hydrant services only |
|
Reducing |
Fabricated steel with fusion epoxy and S.S. nuts and bolts. |
Smith-Blair: #622 – ALL PIPE Mueller MJ: H-619 - ACP |
|
Reducing |
Fabricated all stainless steel with drop in bolts |
Romac: SST - ALL PIPE Smith-Blair: #665 - ALL PIPE Powerseal: #3490AS – ALL PIPE |
|
FLANGED COUPLING ADAPTER |
|||
Epoxy |
Romac: FCA 501 Smith-Blair: 912 (new style) |
||
FLEX COUPLINGS / TRANSITIONS |
|||
AC, DIP, CML&C, PVC |
Romac: Alpha (restrained), Macro HP Smith Blair: 441 PowerSeal: 3506 |
MegaLug, Uni-Flange or TUFGrip on DIP transition, as approved |
|
WATER DISTRIBUTION PIPE |
|||
Ductile Iron Pipe (DIP)* Class: x pressure |
TJ, MJ |
per approved plans |
|
Cement Mortar Lined and Coated (CLM&C) 10 gauge steel pipe |
per approved plans |
||
Polyvinyl Chloride (PVC) C900, DR14 |
per approved plans 6” – 12' dia. |
||
* 8 mil clear polyethylene pipe sleeve on outside |
|||
SEWER PIPE |
|||
PVC Pipe (12" and smaller) | D-3034 SDR 35, Green | class per depth | |
PVC Pipe (14" - 36") |
SDR 26, Green or DR-14 | As approved by the District Engineer | |
|
|
|
|
* 8 mil clear polyethylene pipe sleeve on outside |
|||
SEWER LATERALS |
|||
PVC Pipe |
D-3034 SDR 35 |
||
* 8 mil clear polyethylene pipe sleeve on outside |
|||
MISCELLANEOUS |
|||
Ductile Iron Pipe (DIP) |
6" non-det tape |
||
CML&C Steel Pipe |
6" non-det tape |
||
PVC Water 3M DBY-6 Direct Bury Splice Kit (600 Volts) |
APPROVAL REQUIRED |
6" det tape 10 ga. Solid blue tracer wire |
|
Grounding Clamps | LH Dottie DB 25 or approved equal | ||
Anode: CP-Z15 (15lbs) | Northtown Company | Per Manufacturer Recommendation | |
Snake Pit: Tracer Wire | Copperhead – CD14*2T-SW | Specify Color Blue | |
PVC Sewer | 6" det tape | ||
Tencate Mirafi | 140N or approved equal | ||
|
|||
Ductile Iron Fittings, cement lined, C-110 or C-153 |
Star / Union Foundry Sigma - water only |
Lining per approved plans. I.D. same as main (sewer). |
|
Paint |
Silicone PolyPlus - FCS Coatings Blue: “Nat’l Blue” Yellow: “Safety Yellow” |
FSC phone: (800) 579-8459 |
NOTES:
- All materials listed shall be installed in accordance with the most recent edition of the “Standard Specifications for Construction of Water and Sewer Facilities” of the Vallecitos Water District.
- Intentionally Left Blank - For Future Use